Skip to main content
Siemens 3VA1063-3ED42-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1063-3ED42-0AD0 SENTRON MCCB, 63 A, 4-Pole, 75.6

MPN3VA1063-3ED42-0AD0

Siemens SENTRON 3VA1063-3ED42-0AD0, Molded case circuit breaker, Line protection, 4-pole, 63 A, 75.6 kA at 240 V, TM210 release, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1063-3ED42-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1063-3ED42-0AD0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V7.5 kA
3VA1063-3ED42-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1063-3ED42-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1063-3ED42-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1063-3ED42-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1063-3ED42-0AD0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1063-3ED42-0AD0 is a 4-pole molded case circuit breaker rated for line protection, carrying a continuous current Iu of 63 A up to 50 °C ambient — at 55 °C it derates to 60.48 A, at 60 °C to 59.22 A, at 65 °C to 57.96 A, and at 70 °C to 56.7 A, so the thermal curve is what governs the actual load you can protect in a warm enclosure. Interrupting capacity is specified at four voltages: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V. The 690 V rating of 7.5 kA is lower but still sufficient for most 690 V motor circuits where the transformer impedance limits the prospective fault. No trip indicator on the front face, so the auxiliary contacts are the only way to distinguish a trip from a manual open.

Sourcing and lifecycle — active production, quoted to order

Dimensions: 130 mm height, 101.6 mm width, 70 mm depth.

Frequently asked questions

Where can I buy 3VA1063-3ED42-0AD0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the interrupting capacity of 3VA1063-3ED42-0AD0 at 415 V?

At 415 V the interrupting capacity is 52.5 kA. At 240 V it is 75.6 kA, at 440 V it is 32 kA, and at 690 V it is 7.5 kA.

Does 3VA1063-3ED42-0AD0 include auxiliary contacts?

Yes, it is fitted with 3 auxiliary switches (HQ type) for remote status indication. There is no trip indicator on the front face.

MPN
3VA1063-3ED42-0AD0