Siemens 3VA1063-3ED42-0DA0 SENTRON MCCB, 63 A, 4-Pole

MPN3VA1063-3ED42-0DA0

Siemens SENTRON 3VA1063-3ED42-0DA0, molded case circuit breaker, 4-pole, 63 A, TM210 thermal-magnetic release, line protection version, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1063-3ED42-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1063-3ED42-0DA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V7.5 kA
3VA1063-3ED42-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1063-3ED42-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1063-3ED42-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1063-3ED42-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1063-3ED42-0DA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

It breaks 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V — the interrupting rating drops as voltage climbs, which is typical for MCCBs and means you size it to the available fault current at the actual line voltage.

Thermal derating — what the 63 A rating really means

At 55 °C it derates to 60.48 A, at 60 °C to 59.22 A, at 65 °C to 57.96 A, and at 70 °C to 56.7 A. The rated insulation voltage is 800 V, and the operating temperature range spans -25 °C to 70 °C, with storage from -40 °C to 80 °C — wide enough for most indoor industrial environments but verify the low end if the panel sits in an unheated space.

Release and auxiliary options on this variant

The UVR will trip the breaker if control voltage drops, which is useful for emergency-stop chains or undervoltage protection on motor feeders. The integrated auxiliary trip is a separate order code (3VA9608-0BB25) — not included on the breaker. If you need a shunt trip or auxiliary contacts, you add them as field-installable accessories.

No official successor has been issued for this order code, which is consistent with an active catalog line.

Frequently asked questions

Where can I buy 3VA1063-3ED42-0DA0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA1063-3ED42-0DA0 at 415 V?

At 415 V the breaking capacity is 52.5 kA.

Does 3VA1063-3ED42-0DA0 include an undervoltage release?

Yes, this variant ships with an undervoltage release (UVR) as the auxiliary release.