Thermal derating — the real continuous current at your panel temp
At 55 °C it derates to 60.48 A, at 60 °C to 59.22 A, at 65 °C to 57.96 A, and at 70 °C to 56.7 A. The rated insulation voltage Ui is 800 V, and the operating range is -25 °C to 70 °C, with storage from -40 °C to 80 °C.
The 3-pole footprint is standard for a 63 A MCCB; it occupies three module widths on the rail. The auxiliary contact version is 2 switches HQ, which plug into the front accessory slot.