Line protection MCCB with TM210 release and shunt trip
Breaking capacity varies by system voltage: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V.
Above 55 °C it begins a gradual derating: 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C.
Width 76.2 mm, height 130 mm, depth 70 mm. The 76.2 mm width (3-pole) matches the standard SENTRON 3VA base; it occupies three 25.4 mm module spaces on a DIN rail. The 2 auxiliary switches (HQ type) and shunt trip are factory-integrated; no field-assembly of accessories needed for those functions.