63 A MCCB with high interrupting capacity for line protection
Its interrupting capacity reaches 121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V — meaning it can safely clear high-fault currents at common distribution voltages without upstream cascading. The TM210 release is fixed (non-adjustable thermal and magnetic trip), suited for straightforward feeder protection where you set it and forget it.
Above that, it derates gradually: 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C. Dimensions are 130 mm high × 76.2 mm wide × 70 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures. Latching endurance is rated at 15,000 cycles. No undervoltage release, no communication module, no phase-failure detection on this variant.