Skip to main content
Siemens 3VA1063-4ED36-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1063-4ED36-0CA0 SENTRON MCCB, 63A, 3-Pole, TM210,

MPN3VA1063-4ED36-0CA0

Siemens SENTRON 3VA1063-4ED36-0CA0, molded case circuit breaker, 3-pole, 63 A, TM210 thermal-magnetic overcurrent release, undervoltage release, line protection design, 121 kA interrupting at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1063-4ED36-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10634ED360AA0
3VA1063-4ED36-0CA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C62 A
Current at 60 °C61 A
Current at 65 °C60 A
Current at 70 °C58 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.19.8 W
3VA1063-4ED36-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1063-4ED36-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1063-4ED36-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1063-4ED36-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1063-4ED36-0CA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

63 A SENTRON MCCB with undervoltage release

The Siemens 3VA1063-4ED36-0CA0 is a SENTRON molded case circuit breaker rated for continuous current of 63 A at 40 °C, with no derating needed up to 50 °C — it holds the full 63 A at 50 °C, then tapers to 58 A at 70 °C. That's a solid thermal curve for a warm panel. Three-pole construction with a TM210 thermal-magnetic trip unit. The interrupting capacity hits 121 kA at 240 V, 75.6 kA at 415 V, and still clears 11.9 kA at 690 V — that's high-fault headroom for a 63 A frame.

Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — a standard 3-pole MCCB footprint that mounts directly to a backplate or DIN rail adapter. The UVR coil terminals are accessible on the front face; verify polarity and control voltage before energizing.

Frequently asked questions

Where can I buy 3VA1063-4ED36-0CA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Submit an RFQ for current pricing and availability — confirmed at quote time.

What is the interrupting capacity of 3VA1063-4ED36-0CA0 at 240 V?

It is rated 121 kA at 240 V, with 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V.

Does 3VA1063-4ED36-0CA0 include an undervoltage release?

Yes, it ships with an undervoltage release (UVR) as standard — the auxiliary release design is listed as undervoltage release type.

MPN
3VA1063-4ED36-0CA0