Siemens 3VA1063-4ED36-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1063-4ED36-0CH0 SENTRON MCCB, 63 A, 3-Pole, 121 k

MPN3VA1063-4ED36-0CH0

Siemens SENTRON 3VA1063-4ED36-0CH0, molded case circuit breaker, 3-pole, 63 A, line protection, TM210 release, 121 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1063-4ED36-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1063-4ED36-0CH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1063-4ED36-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1063-4ED36-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1063-4ED36-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3

Environmental

3VA1063-4ED36-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1063-4ED36-0CH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

MCCB for line protection — 63 A, 3-pole, TM210 release

The Siemens SENTRON 3VA1063-4ED36-0CH0 is a 3-pole molded case circuit breaker rated for a continuous current of 63 A at 40 °C, with the TM210 thermal-magnetic release tuned for line protection. The interrupting capacity reaches 121 kA at 240 V and 75.6 kA at 415 V, giving selectivity headroom for most distribution panels. The 70 mm depth and 76.2 mm width fit standard MCCB mounting footprints in enclosures.

Current derating and thermal limits

Rated continuous current holds at 63 A from 40 °C through 50 °C ambient. Above that, derating is progressive: 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C. The operating temperature range spans -25 °C to 70 °C, with storage from -40 °C to 80 °C.

Auxiliary contacts and undervoltage release

This MCCB ships with 2 auxiliary switches plus 1 trip alarm switch (HQ version) and an integrated undervoltage release (UVR). The UVR coil is designed for undervoltage protection; the auxiliary contact set provides status feedback for PLC or indication circuits. The auxiliary release order code is 3VA9608-0BB24.

Frequently asked questions

How do I get current pricing and availability for 3VA1063-4ED36-0CH0?

Submit an RFQ through the storefront; the part is sourced to order and pricing is confirmed at quote time.

What is 3VA1063-4ED36-0CH0's listed depth?

The depth is 70 mm.

What is 3VA1063-4ED36-0CH0's listed width?

The width is 76.2 mm.

MPN