Skip to main content
Siemens 3VA1063-4ED36-0DC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1063-4ED36-0DC0 SENTRON MCCB, 63 A, 3-Pole, 121 k

MPN3VA1063-4ED36-0DC0

Siemens SENTRON 3VA1063-4ED36-0DC0, molded case circuit breaker, 3-pole, 63 A rated continuous current, TM210 overcurrent release, 121 kA at 240 V, 75.6 kA at 415 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1063-4ED36-0DC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1063-4ED36-0DC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1063-4ED36-0DC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1063-4ED36-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1063-4ED36-0DC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2

Environmental

3VA1063-4ED36-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1063-4ED36-0DC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1063-4ED36-0DC0 is a 3-pole molded case circuit breaker rated for 63 A continuous current at 40 °C, with a TM210 thermal-magnetic overcurrent release. It's a line-protection device — no ground-fault monitoring, no communication module, no voltage trigger. The interrupting ratings are 121 kA at 240 V and 75.6 kA at 415 V, which gives you headroom for high-fault panels without cascading upstream. The 70 mm depth and 76.2 mm width fit standard MCCB footprints on a DIN rail or panel-mount base.

Current rating and thermal derating

Rated continuous current Iu is 63 A, and it holds that rating from 40 °C through 50 °C. At 55 °C it derates to 60.48 A, at 60 °C to 59.22 A, at 65 °C to 57.96 A, and at 70 °C to 56.7 A. If your panel ambient runs above 50 °C, size the load side accordingly — the breaker won't trip early, but you lose about 6 A headroom at the top of the operating range.

Interrupting capacity and selectivity

The 3VA1063-4ED36-0DC0 delivers 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V. That 75.6 kA at 415 V is the figure to check for most European industrial panels — it's well above typical utility fault levels, so you can coordinate downstream breakers without worrying about the main failing to clear a bolted fault. The rated insulation voltage is 800 V, which covers 690 V line-to-line systems with margin.

Auxiliary contacts and undervoltage release

Comes with 2 auxiliary switches (HQ version) and an integrated undervoltage release (UVR). The UVR is wired separately — if the control voltage drops, the breaker trips. That's useful for emergency-stop circuits or undervoltage protection on motor feeders. The auxiliary switches give you status feedback to a PLC or indicator lamp without adding an external contact block. The integrated auxiliary trip order code is 3VA9608-0BB25, which is the factory-fit accessory if you need to replace it.

Physical fit and panel integration

Dimensions: 130 mm height, 76.2 mm width, 70 mm depth. That's a standard 3-pole MCCB footprint — fits the same cutout and DIN-rail adapter as other SENTRON 3VA breakers. IP40 on the front means it's protected against tools and wires >1 mm, but not against dust ingress; mount it inside an enclosure if the environment is dirty. Storage range is -40 °C to 80 °C, so it can sit in an unheated warehouse without issue.

Frequently asked questions

How do I get pricing and availability for 3VA1063-4ED36-0DC0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What are the interrupting ratings for 3VA1063-4ED36-0DC0?

121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V. The 75.6 kA at 415 V is the key figure for most European industrial panels.

What is the rated continuous current and derating?

63 A at 40 °C through 50 °C. It derates to 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C.

What auxiliary contacts and releases are included?

It has 2 auxiliary switches (HQ version) and an integrated undervoltage release (UVR). The auxiliary trip order code is 3VA9608-0BB25.

What are the physical dimensions of 3VA1063-4ED36-0DC0?

130 mm height, 76.2 mm width, 70 mm depth. IP40 on the front. Storage range -40 °C to 80 °C.

MPN
3VA1063-4ED36-0DC0