Skip to main content
Siemens 3VA1063-4ED36-0DH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1063-4ED36-0DH0 SENTRON MCCB, 63 A, 3-Pole, Line

MPN3VA1063-4ED36-0DH0

Siemens SENTRON 3VA1063-4ED36-0DH0, Molded case circuit breaker, 3-pole, 63 A, Line protection, TM210 overcurrent release, 70 mm depth, 76.2 mm width.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1063-4ED36-0DH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1063-4ED36-0DH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1063-4ED36-0DH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1063-4ED36-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1063-4ED36-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3

Environmental

3VA1063-4ED36-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1063-4ED36-0DH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What this MCCB is and what the ratings mean for fit

The Siemens SENTRON 3VA1063-4ED36-0DH0 is a 3-pole molded case circuit breaker (MCCB) rated for 63 A continuous current at 40 °C, with a TM210 thermal-magnetic overcurrent release. Line protection version — no ground-fault or voltage-trip module integrated, so it is sized for straight feeder or branch-circuit duty where you need adjustable thermal and fixed magnetic trip curves. The interrupting ratings are the headline: 121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V. That 121 kA at 240 V means this breaker can safely clear a fault at the full available short-circuit current of a large transformer-fed panel without cascading upstream — it is not a current-limiting device, but it holds its integrity through the full let-through. At 690 V the 11.9 kA figure is the limit; spec it only where the fault current at that voltage stays under that ceiling. Thermal derating is flat from 40 °C to 50 °C at 63 A, then drops to 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C. If the panel ambient runs above 50 °C, the continuous load must be reduced accordingly — the breaker does not derate itself, so the panel designer applies the curve. Rated insulation voltage Ui is 800 V, which covers 480/277 V and 600 V systems with margin. The auxiliary contact block is a 2 NO/NC plus 1 trip-alarm switch (HQ type), wired separately from the undervoltage release (UVR) that is built into this variant. The UVR coil holds at nominal voltage; if the control voltage drops, the breaker trips — standard for emergency-stop or undervoltage protection schemes.

Sourcing and lifecycle — active, quoted to order

The integrated auxiliary trip accessory is order code 3VA9608-0BB25 — that is the factory-matched undervoltage release module. If the UVR fails in the field, order that sub-assembly rather than replacing the whole breaker.

Panel integration — footprint and mounting

Dimensions: 130 mm height, 76.2 mm width (3-pole standard), 70 mm depth. The width is the critical dimension for DIN-rail or screw-mount spacing — three of these side by side occupy 228.6 mm of rail. Depth of 70 mm fits standard enclosure depths of 200 mm or more, leaving room for rear bus bars or cable ducts. Front IP40 protection means the breaker face is splash-resistant but not hose-down rated; install in a panel with an IP54 or better enclosure if washdown is required. Operating temperature range is -25 °C to 70 °C, storage from -40 °C to 80 °C.

Frequently asked questions

Where can I buy 3VA1063-4ED36-0DH0 and get a price?

This MCCB is sourced through independent distribution and quoted to order against an RFQ. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is the interrupting rating at 240 V and 415 V?

At 240 V the interrupting rating is 121 kA; at 415 V it is 75.6 kA. At 440 V it is 52.5 kA, and at 690 V it is 11.9 kA.

What are the physical dimensions of this MCCB?

Height 130 mm, width 76.2 mm, depth 70 mm. The width is the key dimension for panel layout — three units side by side occupy 228.6 mm of DIN rail.

What overcurrent release does this breaker use?

It uses a TM210 thermal-magnetic release. The thermal element is adjustable; the magnetic trip is fixed. No electronic trip unit, no communication function, no ground-fault monitoring.

MPN
3VA1063-4ED36-0DH0