Line protection MCCB with TM210 release
Breaking capacity is 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V, so it can interrupt high fault currents across common distribution voltages without cascading upstream.
Above that, derating is gradual: 60.48 A at 55 °C, 59.22 A at 60 °C, 57.96 A at 65 °C, and 56.7 A at 70 °C.
The front face carries an IP40 protection class — suitable for dry indoor panels where no water spray is expected. No undervoltage release, no shunt trip, no ground-fault monitoring, and no N-conductor protection are fitted on this variant.