Skip to main content
Siemens 3VA1063-4ED42-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1063-4ED42-0CC0 SENTRON MCCB, 63 A, 4-Pole, 121 k

MPN3VA1063-4ED42-0CC0

Siemens SENTRON 3VA1063-4ED42-0CC0, molded case circuit breaker, line protection, 4-pole, 63 A rated continuous current (Iu), TM210 thermal-magnetic release, 121 kA breaking capacity at 240 V AC, undervoltage release, 2 auxiliary switches HQ, IP40 front, 70 mm depth × 101.6 mm width × 130 mm height.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1063-4ED42-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1063-4ED42-0CC0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1063-4ED42-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1063-4ED42-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1063-4ED42-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2

Environmental

3VA1063-4ED42-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1063-4ED42-0CC0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

What the ratings mean for fit

The 3VA1063-4ED42-0CC0 is a 4-pole SENTRON molded case circuit breaker carrying a 63 A rated continuous current (Iu) that holds flat from 40 °C to 50 °C — no derating needed in a typical 40 °C panel. At 55 °C it still delivers 60.48 A, at 60 °C it delivers 59.22 A, at 65 °C it delivers 57.96 A, and at 70 °C it delivers 56.7 A, so you get full 63 A capacity in most standard enclosures without oversizing the frame. Breaking capacity is the headline here: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V. That 121 kA at 240 V means it safely interrupts high-fault currents on the secondary side of a large transformer — useful for main or feeder breakers in industrial panels where available fault current is high. The TM210 thermal-magnetic release is a fixed-trip curve, not electronic, so there is no adjustment dial; the trip curve is set at the factory. The part includes an undervoltage release (UVR) as the auxiliary release design, plus two auxiliary switches HQ (high-quality) for status feedback to a PLC or indication lamp. No ground fault monitoring, no phase failure detection, no communication function — this is a straightforward line-protection MCCB, not a smart breaker. The IP40 rating on the front means it is protected against solid objects over 1 mm but not against water ingress; suitable for dry indoor panel mounting.

Panel integration and mounting

Mounts on a DIN rail or can be screw-mounted via the base. Dimensions: 70 mm deep, 101.6 mm wide, 130 mm tall — fits a standard MCCB slot in a SENTRON distribution board or a third-party enclosure. The 4-pole width (101.6 mm) is roughly 4 modules of 25.4 mm each. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C, so it handles cold warehouses and hot panel summers without issue.

Frequently asked questions

What is the breaking capacity of this MCCB at different voltages?

121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V. These are the interrupting ratings per IEC 60947-2; the 121 kA figure at 240 V makes it suitable for high-fault applications like transformer secondaries or main feeders.

How do I get pricing and availability for 3VA1063-4ED42-0CC0?

Submit an RFQ with your target quantity and lead time. Availability and current pricing are confirmed at quote time through independent distribution channels. No stock count or price is published here.

What are the physical dimensions of this breaker?

Depth is 70 mm, width is 101.6 mm, height is 130 mm. The 4-pole width fits a standard 4-module DIN-rail slot at 25.4 mm per pole.

Does this breaker include an undervoltage release?

Yes, the auxiliary release design is an undervoltage release (UVR). It also includes two auxiliary switches HQ for status feedback.

MPN