Skip to main content
Siemens 3VA1063-4ED42-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1063-4ED42-0CH0 SENTRON MCCB, 63 A, 4-Pole, 121 k

MPN3VA1063-4ED42-0CH0

Siemens SENTRON 3VA1063-4ED42-0CH0, molded case circuit breaker, 4-pole, 63 A rated continuous current, TM210 thermal-magnetic release, line protection version, 121 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1063-4ED42-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1063-4ED42-0CH0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1063-4ED42-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1063-4ED42-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1063-4ED42-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3

Environmental

3VA1063-4ED42-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1063-4ED42-0CH0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

Siemens 3VA1063-4ED42-0CH0 — 63 A 4-Pole SENTRON MCCB, Line Protection

The Siemens SENTRON 3VA1063-4ED42-0CH0 is a 4-pole molded case circuit breaker rated for 63 A continuous current at 40 °C, with the TM210 thermal-magnetic overcurrent release. This is the line protection variant — meaning it's configured for feeder and main distribution protection, not motor or generator duty. The interrupting ratings climb to 121 kA at 240 V and 75.6 kA at 415 V, so it handles high-fault utility feeds without cascading upstream. The 800 V rated insulation voltage (Ui) covers 480 V and 600 V class panels with margin.

Ratings and what they mean for fit

The 63 A rating holds flat from 40 °C through 50 °C — no derating needed in a warm enclosure. At 55 °C it drops to 60.48 A, and at 70 °C it's 56.7 A. That's a gentle slope; you can still run 60 A through it at 60 °C. The SCCR curve matters for selectivity: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V. If your transformer secondary is 480 V with 65 kA available fault current, this breaker covers it with headroom. The 4-pole construction means it switches the neutral as well as the three phases — required for TN-S or IT systems where the neutral is not solidly bonded to ground at the panel.

Integrated auxiliary contacts and undervoltage release

This MCCB ships with 2 auxiliary switches plus 1 trip alarm switch (HQ configuration) already integrated — no separate add-on module to order. The undervoltage release (UVR) is also built in, so the breaker drops out if control voltage falls below the dropout threshold. That's a common spec for safety circuits and emergency-stop chains where loss of control power must open the main feeder. The auxiliary contact version is factory-set; verify the wiring diagram matches your PLC input mapping before panel wiring.

Physical fit and panel integration

Dimensions: 130 mm height, 101.6 mm width, 70 mm depth. The width is a standard 4-pole MCCB footprint — fits existing SENTRON 3VA panel cutouts and busbar systems. Front protection is IP40, so it's suitable for enclosed distribution boards but not washdown environments. The depth of 70 mm leaves room for rear-connected busbars or cable ducts in a standard 200 mm deep enclosure.

Frequently asked questions

Where can I buy 3VA1063-4ED42-0CH0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time, not a published figure.

What is 3VA1063-4ED42-0CH0's interrupting capacity at 415 V?

75.6 kA at 415 V. Also rated 121 kA at 240 V, 52.5 kA at 440 V, and 11.9 kA at 690 V.

What overcurrent release does this MCCB use?

The TM210 thermal-magnetic release — a fixed-trip design with thermal overload and magnetic short-circuit protection. No electronic adjustment or communication module.

Does this breaker include auxiliary contacts?

Yes, factory-integrated: 2 auxiliary switches plus 1 trip alarm switch (HQ configuration). Also includes an undervoltage release.

MPN
3VA1063-4ED42-0CH0