Skip to main content
Siemens 3VA1063-4ED42-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1063-4ED42-0DA0 SENTRON MCCB, 63A, 4-Pole, 121kA

MPN3VA1063-4ED42-0DA0

Siemens SENTRON 3VA series molded case circuit breaker, 3VA1063-4ED42-0DA0, 4-pole, 63 A rated at 40 °C, 121 kA breaking capacity at 240 V AC, with undervoltage release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1063-4ED42-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10634ED420AA0

Ratings

3VA1063-4ED42-0DA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C62 A
Current at 60 °C61 A
Current at 65 °C60 A
Current at 70 °C58 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.19.8 W

Protection & Trip Unit

3VA1063-4ED42-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1063-4ED42-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1063-4ED42-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VA1063-4ED42-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1063-4ED42-0DA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

63 A MCCB with undervoltage release — SENTRON 3VA line protection

The Siemens 3VA1063-4ED42-0DA0 is a 4-pole molded case circuit breaker from the SENTRON 3VA series, designed for line protection in distribution panels. It carries a continuous current rating of 63 A at 40 °C (derated to 58 A at 70 °C) and a rated insulation voltage of 800 V. Breaking capacity is 121 kA at 240 V AC, 75.6 kA at 415 V, and 52.5 kA at 440 V — figures that cover most low-voltage fault scenarios in industrial and commercial mains. The TM210 thermal-magnetic overcurrent release handles the overload and short-circuit protection curves. An integrated undervoltage release (UVR) is fitted as standard, so the breaker trips automatically when supply voltage drops below a threshold — useful for motor control centers or safety circuits that require loss-of-voltage protection. Dimensions are 130 mm high, 101.6 mm wide, and 70 mm deep — a standard 4-pole MCCB footprint that fits most Siemens 3VA panelboards and retrofit cutouts.

Current production — sourcing and lifecycle

Maximum power loss is 19.8 W — a figure to factor into enclosure thermal calculations when grouping several breakers in a panel. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. The breaker is rated for use in unconditioned enclosures within those limits.

Selectivity and coordination notes

With a 63 A frame and high interrupting ratings (121 kA at 240 V, 75.6 kA at 415 V), this MCCB is suited for main or feeder positions where fault current is substantial. The TM210 release provides thermal-magnetic protection — no electronic adjustment, but the fixed curve is well-characterized for coordination with downstream 3VA or 5SY series breakers. No communication function or ground-fault monitoring is built in; those capabilities require a different variant (3VA11 or 3VA12 with electronic release).

Frequently asked questions

What is the breaking capacity of 3VA1063-4ED42-0DA0 at 415 V?

75.6 kA at 415 V AC. At 240 V it is 121 kA, at 440 V it is 52.5 kA, and at 500 V or 690 V it is 11.9 kA.

Does this MCCB include an undervoltage release?

Yes, it is fitted with an undervoltage release (UVR) as standard. The overcurrent release is a TM210 thermal-magnetic type.

Where can I buy 3VA1063-4ED42-0DA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA1063-4ED42-0DA0