The Siemens 3VA1063-4ED42-0JH0 is a SENTRON molded case circuit breaker (MCCB) rated for 63 A continuous at 40 °C, carrying that full rating up to 50 °C before it starts to derate — 62 A at 55 °C, 61 A at 60 °C, 60 A at 65 °C, 58 A at 70 °C. That thermal curve means you can load it to nameplate in most ventilated enclosures without bumping into the derate. The interrupting ratings tell you where this breaker can go: 121 kA at 240 VAC, 75.6 kA at 415 VAC, 52.5 kA at 440 VAC, and 11.9 kA at both 500 V and 690 VAC. At 415 V the 75.6 kA still covers most industrial transformer secondaries. Four poles, rated insulation voltage 800 V, line protection design — this is a straight feeder or branch breaker, not a motor-protective device. The 17.3 W max power loss matters for thermal coordination in a sealed enclosure; account for it in your heat budget.

Siemens 3VA1063-4ED42-0JH0 SENTRON MCCB, 63 A, 4-Pole, 121 k
Siemens SENTRON 3VA1063-4ED42-0JH0, molded case circuit breaker (MCCB), 4-pole, 63 A rated current, breaking capacity 121 kA at 240 VAC, line protection design, with shunt trip and auxiliary switches.
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Basic switch (supplied) ref. | 3VA10634ED420AA0 |
| Integrated auxiliary / alarm switch ref. | 3VA9988-0AB12 |
| Parameter | Value |
|---|---|
| Number of poles | 4 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 63 A |
| Current at 45 °C | 63 A |
| Current at 50 °C | 63 A |
| Current at 55 °C | 62 A |
| Current at 60 °C | 61 A |
| Current at 65 °C | 60 A |
| Current at 70 °C | 58 A |
| Switching capacity class | S |
| Breaking capacity at 240 V | 121 kA |
| Breaking capacity at 415 V | 75.6 kA |
| Breaking capacity at 440 V | 52.5 kA |
| Breaking capacity at 500 V | 11.9 kA |
| Breaking capacity at 690 V | 11.9 kA |
| Power loss, max. | 17.3 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | TM210 |
| Overcurrent protection function | LI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | nut keeper kit on both ends |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | Yes |
| Trip indicator | Yes |
| Communication function | No |
| Measurement function | No |
| Motor drive option | No |
| Auxiliary CO contacts | 3 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 20 000 |
| Height | 130 mm |
| Width | 101.6 mm |
| Depth | 70 mm |
| Height (in) | 5.12 in |
| Width (in) | 4 in |
| Depth (in) | 2.76 in |
Product details
Frequently asked questions
What is the breaking capacity of 3VA1063-4ED42-0JH0 at different voltages?
121 kA at 240 VAC, 75.6 kA at 415 VAC, 52.5 kA at 440 VAC, and 11.9 kA at both 500 V and 690 VAC.
Does this MCCB come with auxiliary switches and a shunt trip?
Yes, factory-fitted with 2 auxiliary switches plus 1 trip alarm switch (HQ) and a shunt trip release (STL).
How do I get current pricing and availability for 3VA1063-4ED42-0JH0?
Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.