Skip to main content
Siemens 3VA1063-4ED46-0AA0

Siemens 3VA1063-4ED46-0AA0 SENTRON MCCB, 63 A, 4-Pole, TM210

MPN 3VA1063-4ED46-0AA0
Active

Siemens SENTRON 3VA1063-4ED46-0AA0, molded case circuit breaker, 4-pole, 63 A rated current, TM210 thermal-magnetic overcurrent release, breaking capacity 121 kA at 240 V AC, IP40 front protection.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3VA1063-4ED46-0AA0 specifications
ParameterValue
Poles4
Depth70 mm
Width101.6 mm
Height130 mm

Product details

Product overview and key ratings

It carries a 63 A rated current at 40 °C through all four poles, with no derating needed up to 50 °C — at 55 °C it still holds 62 A, and at 70 °C it delivers 58 A.

Breaking capacity and application context

Breaking capacity is rated per the evidence at 121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. The 4-pole configuration suits three-phase systems with a fully switched neutral, common in North American and IEC distribution.

Dimensions are 130 mm height, 101.6 mm width, and 70 mm depth. The width of 101.6 mm (4 inches) is the standard footprint for a 4-pole MCCB in the SENTRON 3VA frame, so it fits existing panel cutouts and busbar layouts designed for that pole count.

The SENTRON 3VA series carries full IEC/EN 60947-2 certification for molded case circuit breakers. The rated insulation voltage is 800 V, and the operating temperature range spans -25 °C to +70 °C, with storage from -40 °C to +80 °C. Maximum power loss is 17.3 W. The breaker does not include an undervoltage release, trip indicator, or ground-fault monitoring — these are external accessories if required.

MPN