It's sized for 80 A continuous at 40 °C and holds that rating through 50 °C before a gentle thermal derating curve kicks in — 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, 74 A at 70 °C. That means in a warm panel you still get nearly full ampacity without stepping up a frame size. Breaking capacity runs from 52.5 kA at 240 V down to 7.5 kA at 690 V, with intermediate points at 32 kA (415 V) and 13.6 kA (440 V). Front-side protection is IP40 — fine for a clean panel, not for washdown.
Footprint is 76.2 mm wide, 130 mm tall, 70 mm deep — standard 3-pole MCCB spacing that drops into a SENTRON distribution board or a DIN-rail adapter without re-drilling the backplate.