Siemens 3VA1080-2ED32-0AE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1080-2ED32-0AE0 SENTRON MCCB, 80 A, 52.5 kA at 24

MPN3VA1080-2ED32-0AE0

Siemens SENTRON 3VA1080-2ED32-0AE0, molded case circuit breaker, 3-pole, 80 A, TM210 release, 52.5 kA at 240 V, 70 mm depth.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1080-2ED32-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1080-2ED32-0AE0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C76.8 A
Current at 60 °C75.2 A
Current at 65 °C73.6 A
Current at 70 °C72 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1080-2ED32-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1080-2ED32-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1080-2ED32-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts4
3VA1080-2ED32-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1080-2ED32-0AE0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

80 A MCCB with TM210 — line protection for distribution panels

The Siemens SENTRON 3VA1080-2ED32-0AE0 is a 3-pole molded case circuit breaker (MCCB) rated for 80 A continuous current at 40 °C, with no derating needed up to 50 °C — it holds the full 80 A through that range. Above 55 °C it steps down: 76.8 A at 55 °C, 75.2 A at 60 °C, 73.6 A at 65 °C, and 72 A at 70 °C. The TM210 thermal-magnetic overcurrent release handles the time-current curve, adjustable to a maximum delay of 1 s (tr max). It is designed for straightforward feeder and branch-circuit protection in LV distribution.

The interrupting rating drops with system voltage: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V.

At 70 mm deep, 76.2 mm wide, and 130 mm tall, this MCCB fits standard panel-mount cutouts for 3-pole SENTRON frames. No auxiliary release is fitted as standard — the design is listed as without auxiliary release. The TM210 release is fixed-thermal, fixed-magnetic; no voltage trigger.

Frequently asked questions

How do I get current pricing and availability for 3VA1080-2ED32-0AE0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through our independent distribution network.

What is 3VA1080-2ED32-0AE0's listed depth?

The depth is 70 mm. Width is 76.2 mm, height is 130 mm.

What breaking capacity does this MCCB have at 415 V?

At 415 V the interrupting rating is 32 kA. At 240 V it is 52.5 kA, at 440 V it is 13.6 kA, and at 690 V it is 7.5 kA.