Skip to main content
Siemens 3VA1080-2ED32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1080-2ED32-0AH0 SENTRON MCCB, 80 A, 3-Pole, TM210

MPN3VA1080-2ED32-0AH0

Siemens SENTRON 3VA1080-2ED32-0AH0, molded case circuit breaker, 3-pole, 80 A, TM210 thermal-magnetic release, 52.5 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1080-2ED32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1080-2ED32-0AH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C76.8 A
Current at 60 °C75.2 A
Current at 65 °C73.6 A
Current at 70 °C72 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1080-2ED32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1080-2ED32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1080-2ED32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1080-2ED32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1080-2ED32-0AH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What you're looking at

It's a line-protection breaker — no undervoltage release, no ground-fault module, no communication stack. Just the core interrupting job. The interrupting ratings climb as voltage drops: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. That's enough SCCR headroom for most industrial panel feeds — the 415 V figure covers common European and Asian distribution voltages cleanly.

Thermal derating — the real usable current

Above that it starts to step down: 76.8 A at 55 °C, 75.2 A at 60 °C, 73.6 A at 65 °C, and 72 A at 70 °C.

Panel fit and aux contacts

That's a standard MCCB footprint — drops into most DIN-rail or panel-mount bases without re-drilling. That's enough for a remote status signal and a separate alarm contact — useful for feeding a PLC input and a local beacon without sharing terminals.

Frequently asked questions

What does the TM210 trip unit mean on this breaker?

TM210 is a thermal-magnetic release — the thermal element handles overload protection, the magnetic element handles short-circuit protection. No electronic adjustment, no communication.

MPN
3VA1080-2ED32-0AH0