Skip to main content
Siemens 3VA1080-2ED32-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1080-2ED32-0KC0 SENTRON MCCB, 80 A, 3-Pole, TM210

MPN3VA1080-2ED32-0KC0

Siemens SENTRON 3VA1080-2ED32-0KC0, Molded case circuit breaker, Line protection, 3-pole, 80 A (40 °C), TM210 overcurrent release, breaking capacity 52.5 kA at 240 V, with shunt trip and 2 HQ auxiliary switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1080-2ED32-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1080-2ED32-0KC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C76.8 A
Current at 60 °C75.2 A
Current at 65 °C73.6 A
Current at 70 °C72 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1080-2ED32-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1080-2ED32-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1080-2ED32-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1080-2ED32-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1080-2ED32-0KC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Breaking capacity runs 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — so the 240 V figure is the one to check for 208/240 V North American panels, while the 415 V rating governs most European 400 V distribution.

The 80 A rating holds flat from 40 °C through 50 °C, then steps down: 76.8 A at 55 °C, 75.2 A at 60 °C, 73.6 A at 65 °C, and 72 A at 70 °C.

Frequently asked questions

How do I get current pricing and availability for 3VA1080-2ED32-0KC0?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time — the part is sourced to order through independent distribution.

What is 3VA1080-2ED32-0KC0's listed depth (70 mm) on this component line?

The listed depth is 70 mm, width 76.2 mm, height 130 mm — standard 3-pole MCCB footprint for DIN-rail or panel-mount enclosures.

Will 3VA1080-2ED32-0KC0 drop into a panel that was specified around 3VA1010-2ED32-0JA0 without rewiring?

The 3VA1080-2ED32-0KC0 shares the same 3-pole SENTRON platform and identical dimensions (70 mm depth, 76.2 mm width, 130 mm height) as the 3VA1010 frame, so it fits the same mounting footprint and bus-bar spacing. The main difference is the higher continuous current rating (80 A vs 100 A on the 3VA1010) — verify the load and cable sizing before swapping.

MPN
3VA1080-2ED32-0KC0