Breaking capacity runs 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — so the 240 V figure is the one to check for 208/240 V North American panels, while the 415 V rating governs most European 400 V distribution.
The 80 A rating holds flat from 40 °C through 50 °C, then steps down: 76.8 A at 55 °C, 75.2 A at 60 °C, 73.6 A at 65 °C, and 72 A at 70 °C.