Skip to main content
Siemens 3VA1080-2ED36-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1080-2ED36-0BH0 SENTRON MCCB, 80 A, 3-Pole, Line

MPN3VA1080-2ED36-0BH0

Siemens SENTRON 3VA1080-2ED36-0BH0, molded case circuit breaker, 3-pole, 80 A rated continuous current, line protection, with undervoltage release and 2 aux + 1 alarm switch.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1080-2ED36-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA10802ED360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1080-2ED36-0BH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C76.8 A
Current at 60 °C75.2 A
Current at 65 °C73.6 A
Current at 70 °C72 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA

Protection & Trip Unit

3VA1080-2ED36-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1080-2ED36-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1080-2ED36-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3

Environmental

3VA1080-2ED36-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1080-2ED36-0BH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Ratings and deployment context

The 3VA1080-2ED36-0BH0: Rated continuous current Iu is 80 A, with minimal thermal derating up to 50 °C (still 80 A); at 55 °C it drops to 76.8 A, and at 70 °C to 72 A. The rated insulation voltage Ui is 800 V. Front-side protection is IP40 — suitable for enclosed panel mounting, not for washdown or outdoor exposure. Operating temperature range is -25 °C to 70 °C; storage range -40 °C to 80 °C. Dimensions: 130 mm height, 76.2 mm width, 70 mm depth — fits standard 3-pole MCCB panel cutouts.

Frequently asked questions

How do I get current pricing and availability for 3VA1080-2ED36-0BH0?

Submit an RFQ through this listing. The part is sourced to order through independent distribution; availability and current pricing are confirmed at quote time.

When sourcing 3VA1080-2ED36-0BH0, what's the closest functional second-source?

The 3VA1010-2ED32-0JA0 is a smaller-frame sibling in the same SENTRON 3VA family — lower current rating (32 A) and different trip curve, but the same 3-pole line-protection architecture and undervoltage release option. Panel cutout dimensions differ; verify footprint before substituting.

Will 3VA1080-2ED36-0BH0 drop into a panel that was specified around 3VA1010-2ED32-0JA0 without rewiring?

Not without checking the cutout. The 3VA1080 frame is physically larger (130 × 76.2 × 70 mm vs the 3VA1010's smaller footprint), so the panel cutout and busbar spacing must be verified. Wiring terminals are similar but current rating differs — 80 A vs 32 A — so conductor sizing may also need review.

What compliance documentation does this brand provide for 3VA1080-2ED36-0BH0?

Siemens SENTRON MCCBs are designed to meet IEC 60947-2 and UL 489 standards. RoHS and REACH declarations are typically available from the manufacturer's support portal. The reference code per DIN EN 81346-2 is Q.

MPN
3VA1080-2ED36-0BH0