Skip to main content
Siemens 3VA1080-2ED36-0HH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1080-2ED36-0HH0 SENTRON MCCB, 80 A, 52.5 kA

MPN3VA1080-2ED36-0HH0

Siemens SENTRON 3VA1080-2ED36-0HH0, molded case circuit breaker, 3-pole, 80 A rated current (40 °C), 52.5 kA breaking capacity at 240 V, line protection design with shunt trip (STL) and 2 auxiliary + 1 trip alarm switch.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1080-2ED36-0HH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10802ED360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1080-2ED36-0HH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.19.2 W

Protection & Trip Unit

3VA1080-2ED36-0HH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1080-2ED36-0HH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1080-2ED36-0HH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3

Environmental

3VA1080-2ED36-0HH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1080-2ED36-0HH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens SENTRON 3VA1080-2ED36-0HH0 is a 3-pole molded case circuit breaker (MCCB) rated 80 A at 40 °C, with a maximum breaking capacity of 52.5 kA at 240 V. It's configured for line protection and includes a shunt trip (STL) release plus two auxiliary switches and one trip alarm switch (HQ). The insulation voltage is rated 800 V, and maximum power loss is 19.2 W.

Breaking capacity and thermal derating

Breaking capacity drops from 52.5 kA at 240 V to 32 kA at 415 V, then to 13.6 kA at 440 V, and further to 7.5 kA at both 500 V and 690 V. The thermal rating holds at 80 A up to 50 °C, then derates to 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C. That derating curve is what you use for panel ambient — don't size by the 40 °C number alone if your enclosure runs hot.

Panel integration and fit

Dimensions are 70 mm depth, 76.2 mm width (standard 3-pole MCCB footprint), and 130 mm height. The trip indicator and voltage trigger are present; undervoltage release is not fitted. Communication function is absent — this is a standalone thermal-magnetic breaker, not a networked unit.

Frequently asked questions

What is the breaking capacity of 3VA1080-2ED36-0HH0 at different voltages?

Breaking capacity is 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V.

Where can I buy 3VA1080-2ED36-0HH0?

This part is sourced and quoted to order against an RFQ through independent distribution, with availability and current pricing confirmed at quote time.

What auxiliary switches and releases does 3VA1080-2ED36-0HH0 include?

It includes a shunt trip (STL) release, two auxiliary switches, and one trip alarm switch (HQ).

MPN
3VA1080-2ED36-0HH0