It carries an 80 A continuous rating at 40 °C ambient — that's the current it handles without tripping in a typical 40 °C panel environment — and derates slightly to 74 A at 70 °C, so you can still use it in a hot enclosure without oversizing. The TM210 overcurrent release combines a thermal element for overload protection and a magnetic element for short-circuit response.
This MCCB interrupts 52.5 kA at 240 V, 32 kA at 415 V, and 13.6 kA at 440 V.
Panel integration