Skip to main content
Siemens 3VA1080-3ED32-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1080-3ED32-0KC0 SENTRON MCCB, 80 A, 3-Pole, TM210

MPN3VA1080-3ED32-0KC0

Siemens SENTRON 3VA1080-3ED32-0KC0, Molded case circuit breaker, 3-pole, 80 A, TM210 thermal-magnetic release, line protection, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1080-3ED32-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1080-3ED32-0KC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C76.8 A
Current at 60 °C75.2 A
Current at 65 °C73.6 A
Current at 70 °C72 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V7.5 kA

Protection & Trip Unit

3VA1080-3ED32-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1080-3ED32-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1080-3ED32-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2

Environmental

3VA1080-3ED32-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1080-3ED32-0KC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Where it fits in the panel

It's a 76.2 mm wide, 130 mm tall, 70 mm deep unit — a standard three-pole MCCB footprint. Mounts on a DIN rail or screws into a backplate. The IP40 front face means it's fine inside a closed enclosure; keep it away from washdown zones or outdoor weather without a secondary cover. Comes with two auxiliary switches (HQ type) factory-installed — part number 3VA9688-0BL33 for the integrated auxiliary trip. That gives you status feedback to a PLC or a remote annunciator without adding a separate block. No undervoltage release, no shunt trip (STL is a separate accessory), no ground-fault monitor, no phase-failure detection, no communication module. It's a bare-bones line-protection breaker — if you need any of those, you'll add external modules or step up to a 3VA1 with options.

Thermal derating — the real-world number

Rated 80 A continuous at 40 °C, 45 °C, and 50 °C — no derating in that band. At 55 °C it drops to 76.8 A, at 60 °C to 75.2 A, at 65 °C to 73.6 A, and at 70 °C to 72 A. If your panel ambient runs hot (say, next to a drive cabinet or in a sun-baked enclosure), size the load accordingly — don't just read the 80 A nameplate.

Frequently asked questions

Does it include a shunt trip or undervoltage release?

No. The auxiliary release design is a shunt trip (STL) but it's not included — it's a separate accessory. No undervoltage release, no ground-fault monitor, no phase-failure detection, no communication module.

MPN
3VA1080-3ED32-0KC0