Skip to main content
Siemens 3VA1080-3ED36-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1080-3ED36-0BA0 MCCB, 80A, 75.6kA @240V

MPN3VA1080-3ED36-0BA0

Siemens SENTRON 3VA1080-3ED36-0BA0, 3-pole molded case circuit breaker, 80 A, TM210 thermal-magnetic release, undervoltage release, breaking capacity 75.6 kA at 240 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1080-3ED36-0BA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10803ED360AA0

Ratings

3VA1080-3ED36-0BA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.21.7 W

Protection & Trip Unit

3VA1080-3ED36-0BA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1080-3ED36-0BA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1080-3ED36-0BA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VA1080-3ED36-0BA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1080-3ED36-0BA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Product overview

The Siemens SENTRON 3VA1080-3ED36-0BA0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, with an 80 A continuous current rating at 40 °C and a TM210 thermal-magnetic overcurrent release. Breaking capacity reaches 75.6 kA at 240 V AC, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V — giving solid fault-clearing headroom across common industrial voltage levels. Rated insulation voltage is 800 V, and maximum power loss is 21.7 W.

Thermal derating and ambient limits

Current rating holds at 80 A from 40 °C up to 50 °C, then derates to 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C — useful when the breaker sits in a warm enclosure or near other heat sources. Operating temperature range is -25 °C to +70 °C; storage range is -40 °C to +80 °C.

Auxiliary release and integration

Includes an undervoltage release (UVR) as the auxiliary release type, allowing the breaker to trip on loss of control voltage — common in safety circuits or emergency-stop chains. No communication function or ground-fault monitoring version is fitted; this is a straightforward line-protection MCCB for standard distribution panels.

Frequently asked questions

Does this MCCB include an undervoltage release?

Yes, it includes an undervoltage release (UVR) as the auxiliary release type.

MPN
3VA1080-3ED36-0BA0