Rated 80 A continuous at 40 °C and derated to 74 A at 70 °C, so the thermal curve is predictable across a warm enclosure; the TM210 overcurrent release handles the fixed thermal and magnetic trip settings. Breaking capacity sits at 121 kA at 240 V and 75.6 kA at 415 V — that's serious fault current handling for industrial mains, not just light commercial.
Thermal budget and environment
Max power loss is 19.2 W — that's the heat it dumps into the panel at full load, so factor that into your thermal calculation if the box is tight.