Its breaking capacity hits 121 kA at 240 V and 75.6 kA at 415 V, so it handles high-fault utility feeds without cascading upstream.
The 80 A rating holds flat through 50 °C ambient; above that it steps down to 76.8 A at 55 °C and 72 A at 70 °C. The 76.2 mm width and 70 mm depth fit a standard 3-pole MCCB footprint on the DIN rail or panel-mount backplate — no surprises swapping into an existing SENTRON or 3VA cutout.