Skip to main content
Siemens 3VA1080-4ED36-0JH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1080-4ED36-0JH0 SENTRON MCCB, 80A, 3-Pole, 121kA

MPN3VA1080-4ED36-0JH0

Siemens SENTRON 3VA1080-4ED36-0JH0, molded case circuit breaker, 3-pole, 80 A rated current, breaking capacity 121 kA at 240 V, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1080-4ED36-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10804ED360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1080-4ED36-0JH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.19.2 W
3VA1080-4ED36-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1080-4ED36-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1080-4ED36-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1080-4ED36-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1080-4ED36-0JH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What it is and what it does

The Siemens SENTRON 3VA1080-4ED36-0JH0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection in distribution panels. It carries 80 A continuously at 40 °C and derates to 74 A at 70 °C, so the thermal curve is predictable across a typical enclosure ambient range. Breaking capacity is 121 kA at 240 V AC, dropping to 75.6 kA at 415 V and 52.5 kA at 440 V — sufficient for high-fault industrial mains where the available short-circuit current is substantial. At 690 V it still interrupts 11.9 kA, covering most 690 V motor control centers.

Panel integration and fit

The breaker occupies a 76.2 mm wide by 130 mm tall footprint with 70 mm depth behind the panel — standard for a 3-pole SENTRON 3VA frame. Mounts on a DIN rail or directly to a backplate; the compact depth leaves clearance in shallow enclosures. Insulation voltage is rated 800 V, so the breaker is suitable for 690 V line-to-line systems with margin. Power loss at full load is 19.2 W maximum — factor that into enclosure thermal calculations when grouping several breakers.

Auxiliary and release options

This variant ships with two auxiliary switches plus one trip alarm switch (HQ configuration) and a shunt trip release (STL) for remote tripping. The auxiliary contacts are wired to signal breaker status to a PLC or annunciator panel — useful for critical-load monitoring. No undervoltage release, no ground-fault monitoring, and no communication module are fitted on this order code. If those functions are needed, the 3VA family offers alternate variants with UVR, GFI, or PROFIBUS/PROFINET communication — but this specific code is a straight line-protection breaker with shunt trip.

Frequently asked questions

What is the breaking capacity of this MCCB at different voltages?

At 240 V it interrupts 121 kA; at 415 V it interrupts 75.6 kA; at 440 V it interrupts 52.5 kA; at 500 V and 690 V it interrupts 11.9 kA. These ratings cover most industrial mains fault levels.

What is the rated current of 3VA1080-4ED36-0JH0 at elevated temperatures?

It is rated 80 A continuously at 40 °C, 45 °C, and 50 °C. It derates to 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C. Use the 70 °C figure for worst-case enclosure ambient.

Does this breaker include a shunt trip or undervoltage release?

It includes a shunt trip release (STL) for remote tripping. It does not include an undervoltage release or ground-fault monitoring.

Where can I buy 3VA1080-4ED36-0JH0 and what is the lead time?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time.

MPN
3VA1080-4ED36-0JH0