Skip to main content
Siemens 3VA1080-4ED36-0KH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1080-4ED36-0KH0 SENTRON MCCB, 80A, 121kA at 240V

MPN3VA1080-4ED36-0KH0

Siemens SENTRON 3VA1080-4ED36-0KH0, molded case circuit breaker, 3-pole, 80 A rated, 121 kA interrupting at 240 V, line protection design, 70 mm depth.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1080-4ED36-0KH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10804ED360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1080-4ED36-0KH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.19.2 W

Protection & Trip Unit

3VA1080-4ED36-0KH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1080-4ED36-0KH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1080-4ED36-0KH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3

Environmental

3VA1080-4ED36-0KH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1080-4ED36-0KH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1080-4ED36-0KH0 is a 3-pole molded case circuit breaker (MCCB) rated for 80 A continuous at 40 °C, with a line protection design — meaning it's built for feeder and main distribution duty, not motor-starting curves. The interrupting ratings climb to 121 kA at 240 V and 75.6 kA at 415 V, which gives you solid fault-clearing headroom for high-available-fault panels. The insulation voltage is rated 800 V, so it can sit on a 690 V system without derating the dielectric.

Mounts on a standard DIN rail — the 76.2 mm width (3 in) and 70 mm depth (2.76 in) fit a compact enclosure footprint. The supplied basic switch is 3VA10804ED360AA0; the auxiliary switch block carries 2 auxiliary switches plus 1 trip alarm switch (HQ), and the shunt trip (STL) is pre-installed. No undervoltage release on this variant, and no ground-fault monitoring. The trip indicator and voltage trigger are present, so you get local fault annunciation and remote shunt-trip capability out of the box.

Ambient operating range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. The current rating holds steady at 80 A up to 50 °C, then derates linearly to 74 A at 70 °C — useful data for a hot panel or a summer peak load. No communication function on this variant; it's a standalone thermal-magnetic breaker with shunt trip.

Frequently asked questions

What are the key interrupting ratings for 3VA1080-4ED36-0KH0?

At 240 V it interrupts 121 kA; at 415 V it interrupts 75.6 kA; at 440 V it interrupts 52.5 kA; at 500 V and 690 V it interrupts 11.9 kA. The continuous current rating is 80 A at 40 °C.

Where can I buy 3VA1080-4ED36-0KH0 and how is it quoted?

This part is sourced to order through independent distribution channels. Submit an RFQ for current pricing and availability — quotes are confirmed at the time of request.

Will 3VA1080-4ED36-0KH0 drop into a panel specified for 3VA1110-5ED36-0AC0?

The 3VA1080-4ED36-0KH0 is a different frame rating (80 A vs the 3VA1110's higher rating) and different auxiliary configuration. Physical dimensions and DIN-rail footprint are similar across the 3VA family, but verify the interrupting requirements and auxiliary wiring before substitution.

MPN
3VA1080-4ED36-0KH0