Skip to main content
Siemens 3VA1080-4ED42-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1080-4ED42-0HA0 SENTRON MCCB, 80 A, 4-Pole, 121 k

MPN3VA1080-4ED42-0HA0

Siemens SENTRON 3VA1080-4ED42-0HA0, Molded case circuit breaker, 4-pole, 80 A rated continuous current, TM210 overcurrent release, line protection, 121 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1080-4ED42-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1080-4ED42-0HA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C76.8 A
Current at 60 °C75.2 A
Current at 65 °C73.6 A
Current at 70 °C72 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1080-4ED42-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210

Construction & Connection

3VA1080-4ED42-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1080-4ED42-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VA1080-4ED42-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1080-4ED42-0HA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1080-4ED42-0HA0 is a 4-pole molded case circuit breaker (MCCB) rated for 80 A continuous current, with a TM210 thermal-magnetic overcurrent release. It is configured for line protection — no ground-fault monitoring, no auxiliary contacts, no communication function. The interrupting ratings are 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V, which means it can clear high-fault currents at common distribution voltages without upstream coordination issues. The front face carries IP40 protection, suitable for enclosed panel mounting.

The 3VA1080-4ED42-0HA0 measures 130 mm high, 101.6 mm wide, and 70 mm deep. The 4-pole footprint matches standard Siemens 3VA panel cutouts and busbar layouts. It accepts a shunt trip release (order code 3VA9688-0BL30) if remote tripping is needed. No undervoltage release or auxiliary contact module is fitted as shipped — those are add-on accessories. The TM210 release is fixed thermal-magnetic, not electronic, so coordination curves are set at the factory; no field programming required.

Compared to the 3VA1010-2ED32-0JA0, this 3VA1080-4ED42-0HA0 is a higher-current frame (80 A) and carries a 4-pole configuration instead of 3-pole. The 3VA1010-2ED32-0JA0 uses a different release and has a smaller interrupting capacity at equivalent voltages. Panel cutouts differ — the 3VA1080 frame is physically larger, so a direct drop-in without rewiring is not possible.

Frequently asked questions

Does 3VA1080-4ED42-0HA0 include a shunt trip?

It is designed to accept a shunt trip release (order code 3VA9688-0BL30) but does not ship with one fitted. The auxiliary release design is shunt trip (STL).

MPN
3VA1080-4ED42-0HA0