It's a 3-pole line-protection breaker, meaning it's sized for feeder or branch-circuit duty in a distribution panel, not motor-starting applications. At 415 V it still holds 32 kA, and at 690 V it's rated 7.5 kA — that's the voltage-dependent drop you expect from a compact-frame MCCB.
At 55 °C it derates to 15.36 A, at 70 °C to 14.4 A. If your enclosure sits near a heat source or in a non-climate-controlled room, check the actual ambient against that curve.
The TM210 is a thermal-magnetic trip — fixed thermal and magnetic settings, no electronic adjustability. That's fine for a straightforward feeder or branch circuit where coordination is set by the breaker size, not a tunable curve.
The 3VA1096-2ED32-0DA0 measures 130 mm high, 76.2 mm wide, and 70 mm deep. That 76.2 mm width is a 3-pole footprint — it occupies three 25.4 mm modules on a DIN rail or panel-mount base. Standard SENTRON 3VA mounting pattern; it drops into the same cutout as other 3VA frame sizes of the same pole count.