Rated continuous current Iu is 16 A, and it holds that rating flat from 40 °C through 50 °C; above that it derates to 15.36 A at 55 °C and 14.4 A at 70 °C. Breaking capacity runs 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — so the interrupting rating climbs as system voltage drops, which is typical for an MCCB sized for industrial feeder duty. The overcurrent release is a TM210 thermal-magnetic type; a shunt trip (STL) is built in for remote opening.
The 3VA1096-2ED32-0JA0 measures 76.2 mm wide, 130 mm tall, and 70 mm deep.
What the TM210 release and shunt trip mean for the buyer
No electronic adjustment dials — set it and forget it, which is fine for a fixed-load feeder. The shunt trip (STL) lets a PLC, E-stop circuit, or fire-alarm panel trip the breaker remotely; it's wired separately from the power path. No undervoltage release means the breaker won't automatically open on a control-voltage loss — if you need that, this isn't the variant. The auxiliary trip accessory (order code 3VA9688-0BL32) can be added for remote status indication, but the breaker ships without one.