Skip to main content
Siemens 3VA1096-2ED32-0JH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1096-2ED32-0JH0 SENTRON MCCB, 16 A, 3-Pole, 52.5

MPN3VA1096-2ED32-0JH0

Siemens SENTRON 3VA1096-2ED32-0JH0, 3-pole molded case circuit breaker, 16 A rated continuous current (Iu), TM210 thermal-magnetic release, 52.5 kA breaking capacity at 240 V, IP40 front protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1096-2ED32-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1096-2ED32-0JH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C15.36 A
Current at 60 °C15.04 A
Current at 65 °C14.72 A
Current at 70 °C14.4 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1096-2ED32-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1096-2ED32-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1096-2ED32-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1096-2ED32-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1096-2ED32-0JH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Its interrupting ratings hit 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — meaning it clears high-fault currents across common distribution voltages without upstream coordination headaches. Thermal derating is minimal up to 50 °C (holds 16 A flat), then drops to 15.36 A at 55 °C and 14.4 A at 70 °C. The shunt trip (STL) auxiliary release is integrated; order the matching trip unit 3VA9688-0BL32 separately if needed.

Front IP40 rating means it's splash-protected on the panel face but not sealed for washdown environments. The 3-pole footprint matches standard SENTRON 3VA baseplates and busbar systems — retrofit into an existing 3VA cutout without drilling.

Frequently asked questions

Where can I buy 3VA1096-2ED32-0JH0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What breaking capacity does 3VA1096-2ED32-0JH0 have at 415 V?

32 kA at 415 V. It also delivers 52.5 kA at 240 V, 13.6 kA at 440 V, and 7.5 kA at 690 V.

MPN