It carries a 16 A rated current at 40 °C, holds that rating through 55 °C, then derates to 15 A at 60 °C and above — per the datasheet, the thermal curve is flat across the typical panel ambient range, so no headroom adjustment needed unless the enclosure runs hot.
Breaking capacity across voltages
This 3-pole MCCB delivers 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V.
Integrated auxiliaries and release
The two auxiliary switches provide status feedback (open/closed) to a PLC or indication lamp without needing a separate accessory module.
Dimensions: 130 mm height, 76.2 mm width (3 inches), 70 mm depth.