Siemens 3VA1096-3ED32-0CC0 SENTRON MCCB, 16A, 3-Pole, 75.6kA

MPN3VA1096-3ED32-0CC0

Siemens SENTRON 3VA1096-3ED32-0CC0, molded case circuit breaker, 3-pole, 16 A rated current, line protection design, 75.6 kA breaking capacity at 240 V, with undervoltage release and 2 auxiliary switches HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1096-3ED32-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10963ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1096-3ED32-0CC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C16 A
Current at 60 °C15 A
Current at 65 °C15 A
Current at 70 °C15 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.13.1 W
3VA1096-3ED32-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1096-3ED32-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1096-3ED32-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1096-3ED32-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1096-3ED32-0CC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

It carries a 16 A rated current at 40 °C, holds that rating through 55 °C, then derates to 15 A at 60 °C and above — per the datasheet, the thermal curve is flat across the typical panel ambient range, so no headroom adjustment needed unless the enclosure runs hot.

Breaking capacity across voltages

This 3-pole MCCB delivers 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V.

Integrated auxiliaries and release

The two auxiliary switches provide status feedback (open/closed) to a PLC or indication lamp without needing a separate accessory module.

Dimensions: 130 mm height, 76.2 mm width (3 inches), 70 mm depth.

Frequently asked questions

How do I get current pricing and availability for 3VA1096-3ED32-0CC0?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current pricing and availability at the time of your order.

What is the breaking capacity of this MCCB at different voltages?

The 3VA1096-3ED32-0CC0 delivers 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V.

What are the physical dimensions of 3VA1096-3ED32-0CC0?

Height 130 mm, width 76.2 mm (3 inches), depth 70 mm. It is a 3-pole MCCB.

Does this breaker come with an undervoltage release and auxiliary switches?

Yes, it is factory-fitted with an undervoltage release (UVR) and two HQ auxiliary switches.

MPN