Skip to main content
Siemens 3VA1096-3ED32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1096-3ED32-0DA0 SENTRON MCCB, 16 A, 3-Pole, 75.6

MPN3VA1096-3ED32-0DA0

Siemens SENTRON 3VA1096-3ED32-0DA0, molded case circuit breaker, 3-pole, 16 A, breaking capacity 75.6 kA at 240 V AC, line protection design with TM210 overcurrent release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1096-3ED32-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10963ED320AA0
3VA1096-3ED32-0DA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C16 A
Current at 60 °C15 A
Current at 65 °C15 A
Current at 70 °C15 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.13.1 W
3VA1096-3ED32-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1096-3ED32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1096-3ED32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1096-3ED32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1096-3ED32-0DA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1096-3ED32-0DA0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, with a continuous current of 16 A up to 55 °C and 15 A at 70 °C. Breaking capacity drops to 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 500 V and 690 V — the standard derating curve for a 16 A frame.

The 3VA1096-3ED32-0DA0 measures 70 mm deep, 76.2 mm wide, and 130 mm tall — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures without re-drilling. Power loss is 13.1 W maximum, so ventilation in a sealed cabinet is manageable; just don't crowd it against other high-dissipation devices.

Frequently asked questions

What is the breaking capacity of 3VA1096-3ED32-0DA0 at different voltages?

At 240 V it is 75.6 kA, at 415 V it is 52.5 kA, at 440 V it is 32 kA, and at 500 V and 690 V it is 7.5 kA. The 16 A frame derates as system voltage rises.

Where can I buy 3VA1096-3ED32-0DA0 and how is it quoted?

We source this part to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote with lead time.

Will 3VA1096-3ED32-0DA0 drop into a panel specified for 3VA1020-3ED36-0AA0?

Both are 3-pole SENTRON MCCBs in the same physical frame family, so the 70 mm depth, 76.2 mm width, and 130 mm height are identical. No rewiring or enclosure modification should be needed for the mechanical fit, but verify the current rating and trip curve match your circuit design.

MPN
3VA1096-3ED32-0DA0