Skip to main content
Siemens 3VA1096-3ED32-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1096-3ED32-0HC0 SENTRON MCCB, 16A, 3-Pole, 75.6kA

MPN3VA1096-3ED32-0HC0

Siemens SENTRON molded case circuit breaker, 3VA1096-3ED32-0HC0, 3-pole, 16 A rated at 40 °C, breaking capacity 75.6 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1096-3ED32-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10963ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1096-3ED32-0HC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C16 A
Current at 60 °C15 A
Current at 65 °C15 A
Current at 70 °C15 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.10.6 W
3VA1096-3ED32-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1096-3ED32-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1096-3ED32-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1096-3ED32-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1096-3ED32-0HC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Breaking capacity reaches 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — figures that govern its fault-interrupting capability at the point of common coupling.

Breaking capacity drops with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V. Thermal rating holds at 16 A from 40 °C through 55 °C, then derates to 15 A at 60 °C through 70 °C.

Auxiliaries and integration

The supplied basic switch order code is 3VA10963ED320AA0.

Frequently asked questions

Where can I buy 3VA1096-3ED32-0HC0 and get a price?

Sourced to order through independent distribution. Submit an RFQ; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA1096-3ED32-0HC0 at 415 V?

52.5 kA at 415 V. At 240 V it is 75.6 kA; at 440 V it is 32 kA; at 500 V and 690 V it is 7.5 kA.

Does 3VA1096-3ED32-0HC0 include a shunt trip?

Yes. It ships with a shunt trip (STL) and 2 auxiliary switches (HQ type). No undervoltage release or ground-fault monitoring is fitted.

MPN
3VA1096-3ED32-0HC0