Siemens 3VA1096-3ED32-0KA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1096-3ED32-0KA0 SENTRON MCCB, 16 A, 75.6 kA at 24

MPN3VA1096-3ED32-0KA0

Siemens SENTRON 3VA1096-3ED32-0KA0, 3-pole molded case circuit breaker, 16 A rated continuous current, 75.6 kA interrupting at 240 V, line protection with TM210 thermal-magnetic release and shunt trip.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1096-3ED32-0KA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1096-3ED32-0KA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C15.36 A
Current at 60 °C15.04 A
Current at 65 °C14.72 A
Current at 70 °C14.4 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V7.5 kA
3VA1096-3ED32-0KA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1096-3ED32-0KA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1096-3ED32-0KA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1096-3ED32-0KA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1096-3ED32-0KA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Line protection MCCB with 75.6 kA interrupting capacity

Its interrupting capacity hits 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — enough to clear high-fault feeds without cascading upstream. The TM210 thermal-magnetic release handles overload and short-circuit trip curves; a factory-integrated shunt trip (STL) allows remote emergency-off or undervoltage disconnection via the 3VA9688-0BL33 auxiliary trip module.

Carries the full 16 A up to 50 °C ambient; above that it derates linearly to 14.4 A at 70 °C — a useful curve for hot enclosures or furnace-side installations where the breaker shares space with heat-generating gear. IP40 on the front means it tolerates tool contact but not washdown.

Frequently asked questions

Where can I buy 3VA1096-3ED32-0KA0?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the interrupting capacity of this MCCB at different voltages?

75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at 690 V — the high 240 V figure suits North American 277/480 V panel feeds where fault current can exceed 50 kA.

Does 3VA1096-3ED32-0KA0 include a shunt trip?

Yes, it is equipped with a shunt trip (STL) release designed for the 3VA9688-0BL33 auxiliary trip module, enabling remote tripping for emergency stop or undervoltage protection.

What is the thermal derating curve for this breaker?

Full 16 A from 40 °C to 50 °C, then derates to 15.36 A at 55 °C, 15.04 A at 60 °C, 14.72 A at 65 °C, and 14.4 A at 70 °C — plan for a 10 % headroom loss if the breaker sits in a 70 °C enclosure.

MPN
3VA1096-3ED32-0KA0