Skip to main content
Siemens 3VA1096-4ED32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1096-4ED32-0AC0 SENTRON MCCB, 16 A, 3-Pole, 121 k

MPN3VA1096-4ED32-0AC0

Siemens SENTRON 3VA1096-4ED32-0AC0, 3-pole molded case circuit breaker, 16 A, 121 kA at 240 V, TM210 release, line protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1096-4ED32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10964ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1096-4ED32-0AC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C16 A
Current at 60 °C15 A
Current at 65 °C15 A
Current at 70 °C15 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.10.6 W

Protection & Trip Unit

3VA1096-4ED32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1096-4ED32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1096-4ED32-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2

Environmental

3VA1096-4ED32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1096-4ED32-0AC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens 3VA1096-4ED32-0AC0 – 16 A SENTRON MCCB for Line Protection

The Siemens 3VA1096-4ED32-0AC0 is a 3-pole SENTRON molded case circuit breaker (MCCB) designed for line protection, carrying a continuous rated current of 16 A up to 55 °C before derating begins at 60 °C. Its interrupting capacity hits 121 kA at 240 V, dropping to 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V — numbers that tell you this breaker handles high-fault scenarios at lower voltages without cascading upstream. The TM210 thermal-magnetic overcurrent release provides fixed thermal and magnetic trip settings, and the breaker ships with two HQ auxiliary switches for status feedback to a PLC or annunciator panel.

Panel Fit – Dimensions and Integration

At 70 mm deep, 76.2 mm wide, and 130 mm tall, this MCCB fits standard DIN-rail or panel-mount layouts. Rated insulation voltage is 800 V, with an operating temperature range from -25 °C to 70 °C.

Key Ratings – What They Mean for Your Application

The 16 A rating holds steady through 55 °C ambient; at 60 °C it derates to 15 A, and at 70 °C it still carries 15 A — useful if the panel sits near a heat source or in a non-conditioned space. With 121 kA breaking capacity at 240 V, this MCCB can be applied on the secondary side of a 150 kVA transformer feeding a high-fault distribution board, provided the available fault current stays under that number. The 3-pole design with no undervoltage release or ground-fault monitoring keeps it straightforward for straight line protection — no extra coils to fail or nuisance trips to chase.

Frequently asked questions

What is the depth of the 3VA1096-4ED32-0AC0?

The depth is 70 mm (2.76 inches), with a width of 76.2 mm (3 inches) and a height of 130 mm (5.12 inches).

MPN
3VA1096-4ED32-0AC0