Skip to main content
Siemens 3VA1096-4ED32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1096-4ED32-0DA0 SENTRON MCCB, 16A, 3-Pole, 121kA

MPN3VA1096-4ED32-0DA0

Siemens SENTRON 3VA1096-4ED32-0DA0, molded case circuit breaker, 3-pole, 16 A rated at 40 °C, breaking capacity 121 kA at 240 V AC, line protection design with TM210 overcurrent release and undervoltage release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1096-4ED32-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10964ED320AA0
3VA1096-4ED32-0DA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C16 A
Current at 45 °C16 A
Current at 50 °C16 A
Current at 55 °C16 A
Current at 60 °C15 A
Current at 65 °C15 A
Current at 70 °C15 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.13.1 W
3VA1096-4ED32-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1096-4ED32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1096-4ED32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1096-4ED32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1096-4ED32-0DA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

SENTRON 3VA1096-4ED32-0DA0 — 16 A MCCB with undervoltage release

Breaking capacity reaches 121 kA at 240 V AC and 75.6 kA at 415 V AC — figures that put this MCCB well into the high-fault category for North American 240/277 V and European 400 V systems. At 690 V it still interrupts 11.9 kA, so it can serve as a main or branch breaker in 480Y/277 V panels where available fault current exceeds 65 kA.

Current rating holds at 16 A from 40 °C through 55 °C, then steps to 15 A at 60 °C and 65 °C, and stays at 15 A up to the 70 °C maximum operating temperature. That flat derating curve means the breaker can be stacked in a warm enclosure without losing a full amp step until the ambient passes 55 °C. Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — a standard SENTRON 3VA frame that fits Siemens panelboards and DIN-rail adapters. Maximum power loss is 13.1 W, which factors into enclosure thermal calculations when grouping several breakers.

Frequently asked questions

What is the breaking capacity of 3VA1096-4ED32-0DA0 at 415 V?

75.6 kA at 415 V AC. At 240 V it is 121 kA, and at 690 V it is 11.9 kA.

Does 3VA1096-4ED32-0DA0 include an undervoltage release?

Yes, it is equipped with an undervoltage release (UVR) as the auxiliary release type. The overcurrent release is a TM210 thermal-magnetic unit.

Where can I buy 3VA1096-4ED32-0DA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN
3VA1096-4ED32-0DA0