Skip to main content
Siemens 3VA1110-1AA32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-1AA32-0AH0 SENTRON Switch Disconnector, 100

MPN3VA1110-1AA32-0AH0

Siemens SENTRON 3VA1110-1AA32-0AH0, switch disconnector in MCCB design, 3-pole, 100 A rated continuous current, IP40 front, busbar connection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-1AA32-0AH0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1110-1AA32-0AH0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W
3VA1110-1AA32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-1AA32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1110-1AA32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-1AA32-0AH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Switch disconnector, 100 A, no overload protection

It is designed for isolation and switching of circuits where overload or short-circuit protection is handled upstream — there is no integral overcurrent release. Rated operational voltage reaches 690 V AC (50/60 Hz) and 500 V DC, with an insulation voltage (Ui) of 800 V. The unit accepts busbar connection on the main circuit, with front-terminal arrangement.

Dimensions are 70 mm deep by 76.2 mm wide by 130 mm tall — the same footprint as the 3VA1 MCCB frame, so it drops into the same DIN-rail or screw-mount panel cutout.

Frequently asked questions

Where can I buy 3VA1110-1AA32-0AH0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm response.

What is the depth of 3VA1110-1AA32-0AH0?

The depth is 70 mm, with a width of 76.2 mm and height of 130 mm — matching the standard 3VA1 MCCB frame footprint.

Will 3VA1110-1AA32-0AH0 drop into a panel specified for 3VA1110-5ED36-0AC0?

Yes — both share the same 70 mm depth, 76.2 mm width, and 130 mm height, and both use front-terminal busbar connection. The key difference is that 3VA1110-1AA32-0AH0 is a switch disconnector without overcurrent protection, while 3VA1110-5ED36-0AC0 is a molded case circuit breaker with a TM210 thermal-magnetic release. Panel cutout and busbar layout are identical, but the circuit protection function is not.

MPN
3VA1110-1AA32-0AH0