Skip to main content
Siemens 3VA1110-1AA32-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-1AA32-0BH0 SENTRON Switch Disconnector, 100

MPN3VA1110-1AA32-0BH0

Siemens SENTRON 3VA1 IEC frame 160, 3-pole switch disconnector SD100, 100 A, without overload or short-circuit protection, undervoltage release 24 V DC, 2 auxiliary switches HQ + 1 trip alarm switch HQ, busbar connection front terminal.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-1AA32-0BH0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
3VA1110-1AA32-0BH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Power loss, max.38 W
3VA1110-1AA32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-1AA32-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Motor drive optionYes
Auxiliary CO contacts3
3VA1110-1AA32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-1AA32-0BH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1110-1AA32-0BH0 is a SENTRON 3VA1 switch disconnector in an MCCB-style housing, rated for 100 A continuous across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. It is a 3-pole device with no overload or short-circuit protection built in; its job is safe isolation under load, not fault interruption. The integrated undervoltage release (UVR) at 24 V DC drops the contacts if control power is lost, which is standard for emergency-stop or safety-related disconnecting means in a panel. It carries two auxiliary switches (HQ type) plus a separate trip alarm switch — three CO contacts total — so you get status feedback for both the main contact position and any UVR-triggered trip event. The auxiliary switch design is integrated into the front terminal arrangement, which uses busbar connection on the main circuit.

The 3VA1110-1AA32-0BH0 mounts in the standard 3VA1 IEC frame 160 footprint: 70 mm deep, 76.2 mm wide, 130 mm tall. The UVR coil holds at 24 V DC; verify your control transformer sizing if you're feeding multiple releases from the same supply.

Frequently asked questions

Where can I buy 3VA1110-1AA32-0BH0?

This part is sourced to order against an RFQ through independent distribution channels. Submit a request for quote to confirm current availability and pricing.

Will 3VA1110-1AA32-0BH0 drop into a panel specified around 3VA1110-5ED36-0AC0?

The physical dimensions are identical (70 mm deep, 76.2 mm wide, 130 mm high), so it fits the same mounting cutout. However, the 3VA1110-1AA32-0BH0 uses busbar connection on the main circuit, while the 3VA1110-5ED36-0AC0 uses box terminals — you will need to adapt the wiring method.

MPN
3VA1110-1AA32-0BH0