Skip to main content
Siemens 3VA1110-1AA32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1110-1AA32-0DA0 Switch Disconnector, 100

MPN3VA1110-1AA32-0DA0

Siemens SENTRON 3VA1110-1AA32-0DA0, switch disconnector in MCCB design, IEC frame 160, 3-pole, rated continuous current Iu=100 A, max AC operational voltage 690 V, max DC voltage 500 V, undervoltage release (UVR) 208-230 V AC, IP40 front, busbar connection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-1AA32-0DA0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1110-1AA32-0DA0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W
3VA1110-1AA32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-1AA32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1110-1AA32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-1AA32-0DA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1110-1AA32-0DA0 is a 3-pole switch disconnector in an MCCB-style housing — IEC frame 160, rated continuous current Iu of 100 A, and a max AC operational voltage of 690 V at 50/60 Hz. It also handles DC circuits up to 500 V. This is not a circuit breaker: it provides no overload or short-circuit protection. It's a manual disconnect switch for isolating a load under no-fault conditions. Built into the SENTRON 3VA platform, it shares the same 70 mm depth, 76.2 mm width, and 130 mm height as the frame-160 MCCB siblings. The IP40 front protection keeps dust and small tools out of the live parts in a clean panel environment.

The undervoltage release — what it means on the line

That's a standard safety function for motor branch circuits or conveyor lines: if the control power fails, the disconnect opens and the load stops. No leading contact on this UVR version, so it doesn't sequence a downstream contactor. The UVR is factory-installed and wired to the front terminals. There are no auxiliary contacts on this variant (0 CO contacts), and no communication module. If you need remote status feedback or a shunt trip, you're looking at a different 3VA order code.

Where it fits — panel and load considerations

At 76.2 mm wide (roughly 4.5 standard modular units), this switch disconnector takes up the same DIN-rail footprint as a 3-pole 3VA MCCB. Front terminals accept busbar connection — typical for a main disconnect or branch isolator in a distribution panel. The mechanical endurance is 15,000 latching cycles — that's a solid service life for a disconnect that sees a few operations per shift.

Frequently asked questions

Where can I buy 3VA1110-1AA32-0DA0 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — stock levels vary because this is a niche switch-disconnector variant, not a high-volume MCCB.

Will 3VA1110-1AA32-0DA0 drop into a panel specified for 3VA1112-5EF32-0CA0 without rewiring?

Yes, the two share the same 70 mm depth, 76.2 mm width, and 130 mm height, and both use front terminals. But the 3VA1112-5EF32-0CA0 is a full molded-case circuit breaker with a TM240 thermal-magnetic release (125 A), while the 3VA1110-1AA32-0DA0 is a switch disconnector with no overload or short-circuit protection. The mechanical fit is identical; the electrical function is completely different.

What compliance documentation does this part carry?

As a Siemens SENTRON product, it carries CE marking for the European market and is designed to IEC 60947-3 standards for switch-disconnectors. RoHS and REACH declarations are available from Siemens on request. The reference code per DIN EN 81346-2 is Q.

MPN