Skip to main content
Siemens 3VA1110-1AA32-0DH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-1AA32-0DH0 SENTRON Switch Disconnector, 100

MPN3VA1110-1AA32-0DH0

Siemens SENTRON 3VA1110-1AA32-0DH0, switch disconnector in MCCB design, IEC frame 160, 3-pole, 100 A, 690 V AC, undervoltage release 208-230 V AC, 2 aux switches + 1 trip alarm switch, busbar connection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-1AA32-0DH0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
3VA1110-1AA32-0DH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Power loss, max.38 W
3VA1110-1AA32-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-1AA32-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Motor drive optionYes
Auxiliary CO contacts3
3VA1110-1AA32-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-1AA32-0DH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1110-1AA32-0DH0 is a 3-pole switch disconnector in MCCB design, rated at 100 A continuously across the full 40 °C to 70 °C ambient range — no derating needed up to the enclosure's thermal limit. It handles 690 V AC or 500 V DC operating voltage, making it suitable for motor feeder isolation, panel main switches, and load-break applications where overload or short-circuit protection is handled upstream or downstream. Built into the IEC frame 160 footprint, it measures 130 mm high, 76.2 mm wide, and 70 mm deep — a compact 3-pole block that fits standard panel layouts with front-terminal busbar connections for the main circuit.

Integrated auxiliary and release options

This variant ships with an undervoltage release (UVR) rated 208-230 V AC 50/60 Hz, plus 2 HQ auxiliary switches and 1 HQ trip alarm switch — providing three CO contacts total for status feedback to a PLC or indication panel.

Frequently asked questions

How do I get current pricing and availability for 3VA1110-1AA32-0DH0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

Will 3VA1110-1AA32-0DH0 drop into a panel specified around 5SQ2370-2YA05 without rewiring?

No — the 5SQ2370-2YA05 is a miniature circuit breaker (MCB) with different mounting, connection, and protection characteristics. The 3VA1110-1AA32-0DH0 is a switch disconnector in MCCB form factor with busbar connections, not a direct mechanical or electrical substitute.

What are the key ratings of 3VA1110-1AA32-0DH0?

Rated 100 A continuous at 40-70 °C ambient, 690 V AC / 500 V DC operating voltage, 800 V rated insulation voltage, with a maximum power loss of 38 W. The mechanical service life is 15,000 cycles typical.

MPN
3VA1110-1AA32-0DH0