Skip to main content
Siemens 3VA1110-1AA32-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-1AA32-0JA0 SENTRON Switch Disconnector, 100

MPN3VA1110-1AA32-0JA0

Siemens SENTRON 3VA1 IEC frame 160, 3-pole switch disconnector, rated continuous current Iu = 100 A, without overload or short-circuit protection, with shunt trip (STL) 110-127 V DC/AC, busbar front terminal connection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-1AA32-0JA0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1110-1AA32-0JA0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W
3VA1110-1AA32-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-1AA32-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1110-1AA32-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-1AA32-0JA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1110-1AA32-0JA0 is a SENTRON 3VA1 switch disconnector in MCCB design, IEC frame 160, 3-pole, rated for a continuous current Iu of 100 A. It is configured without overload or short-circuit protection — this is a disconnect-only device, not a circuit breaker. The integrated shunt trip (STL) release operates on 110-127 V DC or AC 50/60 Hz, per the product designation.

The 100 A rated continuous current (Iu) sets the maximum load it can carry continuously without exceeding temperature limits. Rated insulation voltage Ui is 800 V, with max operational voltage 690 V AC 50/60 Hz and 500 V DC. That covers standard 400/480 VAC three-phase systems and many DC bus applications up to 500 V. The 2 kA limited short-time withstand (1 s and 0.5 s) tells you this disconnector is rated to hold closed under fault current up to 2 kA for those durations. It is not a breaker — it does not interrupt faults. Upstream protection must clear any fault before the disconnector's short-time rating is exceeded.

Deployment context

This is a panel-mounted switch disconnector for isolating a load circuit. The busbar connection on the front terminals means it integrates into a busbar distribution system — typical for main incomers or large sub-feed disconnects in industrial switchboards. The 76.2 mm width (roughly 4.5 module spaces) and 70 mm depth fit standard SENTRON 3VA1 panel cutouts.

Frequently asked questions

Where can I buy 3VA1110-1AA32-0JA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote — submit an RFQ for a firm price and lead time.

Will 3VA1110-1AA32-0JA0 drop into a panel specified for 3VA1010-2ED32-0JA0 without rewiring?

Both share the same 70 mm depth, 76.2 mm width, 130 mm height, and front terminal arrangement, so the mechanical footprint and busbar connection pattern are identical. The critical difference is function: 3VA1010-2ED32-0JA0 is a molded case circuit breaker with line protection (overload and short-circuit), while 3VA1110-1AA32-0JA0 is a switch disconnector with no overcurrent protection. If the panel design relies on the breaker's protective function, a direct swap is not electrically equivalent — upstream protection must be verified.

What are the key ratings for 3VA1110-1AA32-0JA0?

Rated continuous current Iu = 100 A, 3-pole, rated insulation voltage Ui = 800 V, max operational voltage 690 V AC 50/60 Hz and 500 V DC, short-time withstand 2 kA for 1 s and 0.5 s, max power loss 38 W, IP40 front protection, operating temperature range -25 °C to +70 °C.

MPN
3VA1110-1AA32-0JA0