Skip to main content
Siemens 3VA1110-1AA36-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-1AA36-0AG0 SENTRON Switch Disconnector, 100

MPN3VA1110-1AA36-0AG0

Siemens SENTRON 3VA1110-1AA36-0AG0, switch disconnector in MCCB design, 3-pole, 100 A rated current flat to 70 °C, 690 V AC / 500 V DC, IP40 front, front terminal connection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1110-1AA36-0AG0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON

Ratings

3VA1110-1AA36-0AG0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Power loss, max.38 W

Construction & Connection

3VA1110-1AA36-0AG0 — Construction & Connection
ParameterValue
Main circuit connection typeTerminal connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1110-1AA36-0AG0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1110-1AA36-0AG0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1110-1AA36-0AG0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1110-1AA36-0AG0 is a SENTRON switch disconnector in MCCB design — 3-pole, rated 100 A continuous, with no overload or short-circuit protection built in. It is a straight disconnect, not a breaker; the trip curve is absent because there is no trip unit. What matters for the panel builder is the flat thermal curve: the 100 A rating holds from 40 °C all the way to 70 °C, so no derating is needed in a warm cabinet. That is unusual for a molded-case switch and simplifies the BOM calculation.

Ratings and fit

Rated insulation voltage is 800 V, with operating voltage at 690 V AC and 500 V DC. The front carries IP40 protection — fine for a closed panel, not for washdown. Power loss is 38 W maximum, which is the heat the enclosure must shed. Mechanical service life is 15 000 operating cycles typical. The auxiliary switch configuration is one auxiliary switch plus one trip alarm switch, both HP type, with two CO contacts total. Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a 3-pole MCCB footprint. Front terminal connection with clamp terminals for the main circuit. No undervoltage release, no voltage trigger, no communication function. Motor drive is available as an optional extension.

Frequently asked questions

How do I get current pricing and availability for 3VA1110-1AA36-0AG0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is the closest functional second-source to 3VA1110-1AA36-0AG0?

The 5SQ2370-2YA05 is a different class of device — a 0.5 A miniature circuit breaker, not a 100 A switch disconnector. It will not drop into the same panel position or carry the same load. No direct second-source exists for this MCCB-form switch disconnector.

Will 3VA1110-1AA36-0AG0 drop into a panel specified around 5SQ2370-2YA05?

No. The 5SQ2370-2YA05 is a 55 mm deep MCB; this switch disconnector is 70 mm deep, 76.2 mm wide, and rated 100 A. The footprint, terminal arrangement, and current rating are incompatible.

MPN