Skip to main content
Siemens 3VA1110-1AA36-0DC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-1AA36-0DC0 SENTRON Switch Disconnector, 100

MPN3VA1110-1AA36-0DC0

Siemens SENTRON 3VA1110-1AA36-0DC0, switch disconnector in MCCB design, 3-pole, 100 A rated continuous current, 690 V AC, with undervoltage release 208-230 V AC, 2 auxiliary switches HQ, front terminal connection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1110-1AA36-0DC0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design

Ratings

3VA1110-1AA36-0DC0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W

Construction & Connection

3VA1110-1AA36-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typeTerminal connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1110-1AA36-0DC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1110-1AA36-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1110-1AA36-0DC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1110-1AA36-0DC0 is a 3-pole switch disconnector from the SENTRON family, built in an MCCB form factor. It carries a 100 A rated continuous current (Iu) and is rated for 690 V AC / 500 V DC maximum operational voltage.

What the ratings mean for fit

Rated continuous current Iu = 100 A means this disconnector handles full-load current on a 100 A feeder without derating at 40 °C ambient. The 690 V AC rating covers 400/480 V systems with headroom; the 500 V DC rating suits battery banks or DC bus isolation up to that voltage. The undervoltage release (UVR) is wired to a 208-230 V AC supply — if that control voltage drops, the disconnector trips open. This prevents automatic restart after a brownout. The unit also has two HQ auxiliary switches (form C) for status feedback to a PLC or panel lamp. Front terminal connection means the load and line cables land on the front face — common for panel layouts where side-access is tight. The IP40 front protection keeps tools and fingers out but is not rated for washdown; this is a dry indoor panel part. Mechanical endurance is 15,000 operations — enough for daily switching in a distribution board but not for high-cycle process control. The 2 kA short-time withstand (1 s and 0.5 s) confirms it can ride through a fault until an upstream breaker clears.

Panel integration

Mounts on a DIN rail or panel via the MCCB footprint. Dimensions: 130 mm height, 76.2 mm width, 70 mm depth — fits standard SENTRON 3VA1 cutouts. The front terminal connection accepts lug or clamp terminations; the UVR module occupies the auxiliary slot on the right side.

MPN
3VA1110-1AA36-0DC0