Skip to main content
Siemens 3VA1110-1AA36-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-1AA36-0JA0 SENTRON Switch Disconnector, 100

MPN3VA1110-1AA36-0JA0

Siemens SENTRON 3VA1110-1AA36-0JA0, switch disconnector in MCCB design, IEC frame 160, 3-pole, 100 A, without overload or short-circuit protection, shunt trip (STL) 110-127 V DC/AC 50/60 Hz, front terminal connection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-1AA36-0JA0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
3VA1110-1AA36-0JA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Power loss, max.38 W
3VA1110-1AA36-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typeTerminal connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-1AA36-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1110-1AA36-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-1AA36-0JA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1110-1AA36-0JA0 is a 3-pole switch disconnector in MCCB design, rated at 100 A continuous current across the full operating temperature range from 40 °C to 70 °C — no derating needed up to the 70 °C ceiling. It is built on the IEC frame 160 platform and intended for isolation and switching duty where overload or short-circuit protection is handled separately upstream or by a downstream device.

That covers most 400 V and 480 V distribution panels cleanly, and the DC rating handles battery or UPS circuits up to 500 V. Mechanical service life is 15 000 operating cycles, typical for a disconnect switch in this frame class — fine for infrequent isolation, not for daily motor starting.

It uses front terminal connections for the main circuit, with lug-type terminals. Maximum power loss is 38 W at rated current; plan for that heat dissipation inside the enclosure, especially if multiple units are ganged.

Frequently asked questions

Will 3VA1110-1AA36-0JA0 fit in a panel designed for 3VA1110-5EE32-0JA0?

Yes. Both parts share the same depth (70 mm), width (76.2 mm), and height (130 mm), and both use front terminal connections. Mechanical interchange is direct — no panel modification or rewiring needed.

MPN
3VA1110-1AA36-0JA0