Specifications

Identification

3VA1110-1AA42-0AB0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON

Ratings

3VA1110-1AA42-0AB0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Power loss, max.38 W

Construction & Connection

3VA1110-1AA42-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1110-1AA42-0AB0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1110-1AA42-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1110-1AA42-0AB0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width101.6 mm
Depth70 mm

Product details

What This Part Is and What It Does

The Siemens SENTRON 3VA1110-1AA42-0AB0 is a 4-pole switch disconnector in MCCB design rated for 100 A continuous at up to 70 °C ambient — no derating needed from 40 °C to 70 °C. Rated 690 V AC and 600 V DC, with a rated insulation voltage of 800 V. Main circuit connects via busbar at front terminals — no wire lugs, so it's sized for a busbar drop in a panel. This is a pure disconnect — no overload protection, no short-circuit protection, no undervoltage release, no trip indicator. It's a load-break switch designed for isolation and manual switching, not circuit protection.

Where It Fits in the Panel

Mechanical service life is 15 000 operating cycles typical — solid for a disconnect that sees once-per-shift or maintenance switching. The 2 HP auxiliary contacts (2 CO contacts) are built in, so you get status feedback without an add-on block. Dimensions: 130 mm high, 101.6 mm wide, 70 mm deep. Front face is IP40 — fine for a closed panel; not for washdown zones. Optional motor drive available if you need remote operation. Storage range is -40 °C to 80 °C; operating range -25 °C to 70 °C. The storage limit governs handling and shipping, not running conditions.

Lifecycle and Sourcing Reality

Maximum power loss is 38 W — account for that in the panel thermal budget if you're packing several disconnects in a small enclosure.

Frequently asked questions

Will 3VA1110-1AA42-0AB0 drop into a panel specified for 5SQ2670-2YA06?

No. The 5SQ2670-2YA06 is a 55 mm deep MCB for DIN-rail mounting; the 3VA1110-1AA42-0AB0 is a 70 mm deep MCCB-frame disconnect with busbar connection — different footprint, different mounting, different current class.

What are the key dimensions of 3VA1110-1AA42-0AB0?

Height 130 mm, width 101.6 mm, depth 70 mm. Front terminal busbar connection.