Siemens 3VA1110-1AA42-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-1AA42-0CC0 SENTRON Switch Disconnector, 100

MPN3VA1110-1AA42-0CC0

Siemens SENTRON 3VA1110-1AA42-0CC0, 4-pole switch disconnector, 100 A rated continuous current, undervoltage release 120-127 V AC 50/60 Hz, 2 auxiliary switches HQ, busbar connection, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-1AA42-0CC0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1110-1AA42-0CC0 — Ratings
ParameterValue
Number of poles4
Power loss, max.38 W
3VA1110-1AA42-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-1AA42-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1110-1AA42-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-1AA42-0CC0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

Switch disconnector for load isolation

The Siemens 3VA1110-1AA42-0CC0 is a 4-pole switch disconnector from the SENTRON 3VA1 family, rated for 100 A continuous current (Iu) and designed for IEC frames up to 160 A. It provides visible-break isolation without overload or short-circuit protection — it's a disconnect, not a breaker. Rated insulation voltage is 800 V, and the maximum operational voltage is 690 V AC (50/60 Hz) or 600 V DC. The unit accepts busbar connection on the front terminals, making it suitable for distribution panels where busbar tap-offs feed downstream loads. The IP40 front protection means it's splash-proof from the front but not sealed — mount inside an enclosure for washdown environments.

Dimensions: 130 mm height, 101.6 mm width, 70 mm depth. The width is a standard 4-module footprint for panel-mounting on DIN rail or direct screw fixing. The 70 mm depth leaves clearance for busbar connections and auxiliary wiring behind the panel door.

Environmental and endurance ratings

Frequently asked questions

Where can I buy 3VA1110-1AA42-0CC0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings of 3VA1110-1AA42-0CC0?

Rated continuous current Iu is 100 A, rated insulation voltage Ui is 800 V, maximum operational voltage is 690 V AC or 600 V DC. It is a 4-pole switch disconnector with an undervoltage release.

Will 3VA1110-1AA42-0CC0 drop into a panel specified around 5SQ2670-2YA06?

No. The 5SQ2670-2YA06 is a 4-pole MCB with a different form factor (55 mm depth, IP20) and a 6 A rating. The 3VA1110-1AA42-0CC0 is a 100 A switch disconnector with a 70 mm depth and IP40 front — it is not a direct mechanical or electrical replacement without panel rework.

MPN
3VA1110-1AA42-0CC0