Skip to main content
Siemens 3VA1110-1AA42-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-1AA42-0CC0 SENTRON Switch Disconnector, 100

MPN3VA1110-1AA42-0CC0

Siemens SENTRON 3VA1110-1AA42-0CC0, 4-pole switch disconnector, 100 A rated continuous current, undervoltage release 120-127 V AC 50/60 Hz, 2 auxiliary switches HQ, busbar connection, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1110-1AA42-0CC0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design

Ratings

3VA1110-1AA42-0CC0 — Ratings
ParameterValue
Number of poles4
Power loss, max.38 W

Construction & Connection

3VA1110-1AA42-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1110-1AA42-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1110-1AA42-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1110-1AA42-0CC0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

Switch disconnector for load isolation

The Siemens 3VA1110-1AA42-0CC0 is a 4-pole switch disconnector from the SENTRON 3VA1 family, rated for 100 A continuous current (Iu) and designed for IEC frames up to 160 A. It provides visible-break isolation without overload or short-circuit protection — it's a disconnect, not a breaker. The built-in undervoltage release (UVR) trips the switch when supply voltage drops below a threshold, which is common in safety circuits or emergency-stop chains where loss of control power must open the load. Rated insulation voltage is 800 V, and the maximum operational voltage is 690 V AC (50/60 Hz) or 600 V DC. The unit accepts busbar connection on the front terminals, making it suitable for distribution panels where busbar tap-offs feed downstream loads. The IP40 front protection means it's splash-proof from the front but not sealed — mount inside an enclosure for washdown environments.

Physical fit and integration

Dimensions: 130 mm height, 101.6 mm width, 70 mm depth. The width is a standard 4-module footprint for panel-mounting on DIN rail or direct screw fixing. The 70 mm depth leaves clearance for busbar connections and auxiliary wiring behind the panel door. Two auxiliary switches (HQ type) are integrated, providing status feedback to a PLC or indication lamp without an external add-on block.

Environmental and endurance ratings

Operating temperature range is -25 °C to +70 °C; storage range is -40 °C to +80 °C. Mechanical endurance is rated at 15,000 latching operations. Maximum power loss is 38 W, which should be factored into enclosure thermal calculations if the switch is continuously loaded near its 100 A rating.

Frequently asked questions

Where can I buy 3VA1110-1AA42-0CC0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings of 3VA1110-1AA42-0CC0?

Rated continuous current Iu is 100 A, rated insulation voltage Ui is 800 V, maximum operational voltage is 690 V AC or 600 V DC. It is a 4-pole switch disconnector with an undervoltage release.

Will 3VA1110-1AA42-0CC0 drop into a panel specified around 5SQ2670-2YA06?

No. The 5SQ2670-2YA06 is a 4-pole MCB with a different form factor (55 mm depth, IP20) and a 6 A rating. The 3VA1110-1AA42-0CC0 is a 100 A switch disconnector with a 70 mm depth and IP40 front — it is not a direct mechanical or electrical replacement without panel rework.

MPN
3VA1110-1AA42-0CC0