Siemens 3VA1110-1AA42-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-1AA42-0JC0 SENTRON Switch Disconnector, 100

MPN3VA1110-1AA42-0JC0

Siemens SENTRON 3VA1110-1AA42-0JC0, switch disconnector in MCCB design, IEC frame 160, 4-pole, In=100 A, without overload or short-circuit protection, shunt trip (STL) 110-127 V DC/AC, 2 HQ auxiliary switches, busbar connection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-1AA42-0JC0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
3VA1110-1AA42-0JC0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Power loss, max.38 W
3VA1110-1AA42-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-1AA42-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1110-1AA42-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-1AA42-0JC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width101.6 mm
Depth70 mm

Product details

Rated for 690 V AC or 600 V DC, it serves as a manual load-break disconnect for isolating motor feeders, distribution subfeeds, or machine infeed sections. This variant ships without overload or short-circuit protection — it is a pure disconnect, not a circuit breaker. The integrated shunt trip (STL) coil, rated 110–127 V DC/AC 50/60 Hz, allows remote or emergency-off tripping.

Dimensions are 130 mm high, 101.6 mm wide, and 70 mm deep — a 4-pole MCCB footprint that drops into standard DIN-rail or panel-mount enclosures. Main circuit connections are busbar-type front terminals, which keep wiring organized in multi-feeder panels. A motor-drive option is available as an accessory (field-installable), enabling remote motorized operation for automated disconnection sequences.

Frequently asked questions

What is 3VA1110-1AA42-0JC0's rated current and voltage?

It is rated 100 A continuous (no derating up to 70 °C ambient) at 690 V AC or 600 V DC.

Does this switch disconnector include overcurrent protection?

No — it is a pure disconnect without overload or short-circuit protection. The shunt trip (STL) provides remote tripping capability.

Where can I buy 3VA1110-1AA42-0JC0?

Sourced and quoted to order against an RFQ through independent distribution channels; availability and current pricing are confirmed at quote time.

Will 3VA1110-1AA42-0JC0 drop into a panel specified around 3VA1110-5ED36-0AC0 without rewiring?

No — the 5ED36 variant is a 3-pole molded case circuit breaker with box terminals, while this is a 4-pole switch disconnector with busbar front terminals. Different pole count and connection method mean the panel layout and wiring would need rework.

MPN