Skip to main content
Siemens 3VA1110-1AA42-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-1AA42-0KC0 SENTRON Switch Disconnector, 100

MPN3VA1110-1AA42-0KC0

Siemens SENTRON 3VA1110-1AA42-0KC0 switch disconnector in MCCB design, 4-pole, 100 A rated continuous current, shunt trip STL 220-250 VDC / 208-277 VAC, 2 auxiliary switches HQ, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-1AA42-0KC0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1110-1AA42-0KC0 — Ratings
ParameterValue
Number of poles4
Power loss, max.38 W
3VA1110-1AA42-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-1AA42-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1110-1AA42-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-1AA42-0KC0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

It carries no overload or short-circuit protection — this is a pure disconnect for isolation and switching duty, not a circuit breaker. The shunt trip (STL) release operates on 220-250 VDC or 208-277 VAC, giving you remote trip capability for emergency-stop or process-interlock circuits. Two built-in HQ auxiliary switches report contact position back to the PLC or panel indicators.

The 100 A continuous rating (Iu) defines the maximum load it can carry without overheating — sized for feeder or main disconnect duty on a 100 A circuit. The 800 V rated insulation voltage (Ui) and 690 VAC / 600 VDC max operational voltage (Ue) cover standard 400/480 VAC panels and DC bus applications up to 600 V. Front terminals with busbar connection mean it lands directly on a panel busbar system, not on cable lugs — verify your busbar pitch matches the 101.6 mm width footprint.

Deployment context

Mounts in a standard panel on a busbar system via front terminals. The 70 mm depth fits shallow enclosures. The shunt trip allows integration into safety circuits or remote shutdown schemes — wire it to an E-stop relay or PLC output for controlled disconnection. The two HQ auxiliary switches (CO contacts) provide status feedback for SCADA or local indication. The 15 000-cycle mechanical endurance is typical for a disconnect used in daily switching rather than infrequent isolation.

Frequently asked questions

What is the difference between this switch disconnector and a 3VA1110-5EE32-0JA0 MCCB?

The 3VA1110-1AA42-0KC0 is a pure switch disconnector with no overcurrent protection; the 3VA1110-5EE32-0JA0 is a 3-pole MCCB with a TM220 thermal-magnetic trip unit providing LI protection. The disconnector is 4-pole (101.6 mm wide) versus the MCCB's 3-pole (76.2 mm wide). Both share the same 70 mm depth and 130 mm height.

MPN
3VA1110-1AA42-0KC0